An analysis of structural and practical identifiability applied to a transient generator model

Texto completo
Autor(es):
Landgraf, Taylon G. ; Cari, Elmer P. T. ; Alberto, Luis F. C.
Número total de Autores: 3
Tipo de documento: Artigo Científico
Fonte: Electric Power Systems Research; v. 206, p. 11-pg., 2022-01-28.
Resumo

This article addresses issues of the structural and practical identifiability of a transient model of a synchronous generator. A structural identifiability analysis was conducted for nonlinear models of differential-algebraic equations (DAEs) and then applied to the DAE model of the synchronous generator, whose parameters were estimated by a practical identifiability analysis employing a trajectory sensitivity method. An optimal time window of measurement data was selected for improving the accuracy of the estimated parameters, which were validated from different sets of measurements collected in two different experiments. (AU)

Processo FAPESP: 18/20104-9 - Monitoramento via sincrofasores, análise de segurança dinâmica e controle de redes elétricas do futuro
Beneficiário:Luís Fernando Costa Alberto
Modalidade de apoio: Auxílio à Pesquisa - Temático
Processo FAPESP: 17/09208-4 - Método híbrido para estimar parâmetros de usinas fotovoltaicas
Beneficiário:Elmer Pablo Tito Cari
Modalidade de apoio: Auxílio à Pesquisa - Regular