| Texto completo | |
| Autor(es): |
Modolo, Marcela A.
;
Bento, Murilo E. C.
;
Moraco, Anna G. M.
;
Ratnam, Elizabeth L.
;
Ramos, Rodrigo A.
;
IEEE
Número total de Autores: 6
|
| Tipo de documento: | Artigo Científico |
| Fonte: | 2021 IEEE PES INNOVATIVE SMART GRID TECHNOLOGIES - ASIA (ISGT ASIA); v. N/A, p. 5-pg., 2021-01-01. |
| Resumo | |
The use of synchronized data provided by Phasor Measurement Units (PMUs) installed on system buses in a Wide Area Monitoring, Protection and Control Systems (WAMPAC) has shown to be promising to be used by a Wide-Area Damping Controller (WADC) to improve the well-known inter-area oscillation modes in power systems. However, recent research has demonstrated the vulnerability of PMU measurements to certain types of cyber-attacks such as Denial-of-Service attack that can interfere the proper operation of system devices that rely on reliable data from PMUs as a typical WADC. This research aims to evaluate critical shutdown times for a WADC subject to failures in the communication channels that can compromise its operation. Case studies of the IEEE 7-bus system are presented and discussed. (AU) | |
| Processo FAPESP: | 18/20104-9 - Monitoramento via sincrofasores, análise de segurança dinâmica e controle de redes elétricas do futuro |
| Beneficiário: | Luís Fernando Costa Alberto |
| Modalidade de apoio: | Auxílio à Pesquisa - Temático |