Busca avançada
Ano de início
Entree


Ferroresonance mitigation for the unconventional rural electrification system

Texto completo
Autor(es):
Rojas, R. E. ; Chaves, J. S. ; Tavares, M. C.
Número total de Autores: 3
Tipo de documento: Artigo Científico
Fonte: Electric Power Systems Research; v. 223, p. 7-pg., 2023-10-01.
Resumo

This paper presents a solution to the observed ferroresonance (FRR) phenomenon for both energization switching and load shedding conditions in an unconventional rural electrification system. The energy is extracted from the electric field surrounding an extrahigh voltage transmission line. Ferroresonance occurs in the power transformers of the distribution substation, and the existing solution cannot be directly applied. The mitigation method consists of the insertion of a shunt resistor when the FRR starts. The robustness of the method is shown in a time-domain simulation implemented in PSCAD/EMTDC. (AU)

Processo FAPESP: 22/01896-7 - Contribuição para a área de transitórios eletromagnéticos em sistema de potência com foco no objetivo de desenvolvimento sustentável 07
Beneficiário:Maria Cristina Dias Tavares
Modalidade de apoio: Auxílio à Pesquisa - Regular