| Autor(es): |
Lacerda, Vinicius A.
;
Coury, Denis V.
;
Suzuki, Nayara Y.
;
Monaro, Renato M.
;
IEEE
Número total de Autores: 5
|
| Tipo de documento: | Artigo Científico |
| Fonte: | 2018 POWER SYSTEMS COMPUTATION CONFERENCE (PSCC); v. N/A, p. 7-pg., 2018-01-01. |
| Resumo | |
In Modular Multilevel Converter (MMC) based DC systems, during the initial stage of a DC fault, the control system operates normally, inserting and bypassing submodules. Consequently, each MMC control technique would provide a different characteristic to the DC short-circuit behavior. Therefore, this paper presents a comparative analysis of MMC control techniques, providing a better understanding on how the control techniques impact the fault currents. The analyses were performed by simulating and applying DC faults to a two-terminal VSC-HVDC system with different groups of control techniques. It was found that the DC fault current was not influenced either by control parameters, modulation or output-current control techniques. The arm-balancing control influenced the DC fault currents as it has an impact on the modulation reference signal. (AU) | |
| Processo FAPESP: | 15/21167-6 - Detecção, localização de faltas e proteção inteligente de linhas HVDC com múltiplos terminais |
| Beneficiário: | Vinícius Albernaz Lacerda Freitas |