| Texto completo | |
| Autor(es): |
Martins, P. E. T.
;
Oleskovicz, M.
Número total de Autores: 2
|
| Tipo de documento: | Artigo Científico |
| Fonte: | Electric Power Systems Research; v. 254, p. 11-pg., 2026-05-01. |
| Resumo | |
Given numerous branches in current distribution systems, the fault estimated distance may correspond to several points in the system, often distant from each other. This problem is known as the multiple fault estimation problem and delays the maintenance team's work locating the fault. This research suggests using simple fault location techniques, usually already commercially available, to reduce multiple estimations. The challenge is to find the best positions to install the meters that will provide information to these locators and to define a methodology to aggregate the responses of all these locators coming from the different buses with installed meters. The meters' optimal allocation problem was solved with a multi-objective formulation to minimize the number of meters (cost) and to maximize the number of faults locatable without multiple estimations. The results showed improvements in the fault location rate, reaching more than 30% compared to the weakest fault locator. It demonstrated that even imprecise fault locators can be used together to provide an improved response. To our knowledge, multiple fault locators have never been combined like in our proposal, this being an important contribution to the state of the art. (AU) | |
| Processo FAPESP: | 17/22967-1 - A localização de faltas em microrredes a partir de uma alocação otimizada de medidores |
| Beneficiário: | Mário Oleskovicz |
| Modalidade de apoio: | Auxílio à Pesquisa - Regular |