| Texto completo | |
| Autor(es): |
Número total de Autores: 3
|
| Afiliação do(s) autor(es): | [1] Sao Paulo State Univ, Dept Elect Engn, BR-15385000 Ilha Solteira - Brazil
Número total de Afiliações: 1
|
| Tipo de documento: | Artigo Científico |
| Fonte: | IEEE Transactions on Power Delivery; v. 35, n. 3, p. 1071-1082, JUN 2020. |
| Citações Web of Science: | 0 |
| Resumo | |
This paper proposes an innovative method for dimensioning and designing the zero-sequence electromagnetic filter applied to three-phase four-wire distribution power systems. As premises, the optimum ratio between zero-sequence and positive-sequence impedances of the filter must be established in order to potentiate the filtering percentage of zero-sequence currents and ensure the quality of the supply system displacement power factor. The calculations are based on the sequential harmonic transmittances of the equivalent circuit reduced to the coupling point of the electromagnetic filter. To validate the proposed method, the results obtained with the application of the electromagnetic filter designed in a test system using the MATLAB software are compared to the results of the system modeled in the PSIM software. (AU) | |
| Processo FAPESP: | 15/21972-6 - Otimização do planejamento e da operação de sistemas de transmissão e de distribuição de energia elétrica |
| Beneficiário: | Rubén Augusto Romero Lázaro |
| Modalidade de apoio: | Auxílio à Pesquisa - Temático |