Analysis of Fulfillment of LVRT Requirements under Unbalanced Operating Conditions

Texto completo
Autor(es):
Borges, Rafael C. ; Ramos, Rodrigo A. ; Reginatto, Romeu ; IEEE
Número total de Autores: 4
Tipo de documento: Artigo Científico
Fonte: 2016 IEEE PES TRANSMISSION & DISTRIBUTION CONFERENCE AND EXPOSITION-LATIN AMERICA (PES T&D-LA); v. N/A, p. 6-pg., 2016-01-01.
Resumo

As the wind power penetration continues to increase, wind turbines are required to provide Low Voltage Ride Through (LVRT) capability, thus new grid codes for wind turbines are established. Most grid codes provide the LVRT curve only for the connection to the transmission system. Only few of them include the distribution system and yet the measuring of the terminal voltage do not consider unbalanced operating conditions. This paper analyses the fulfillment of LVRT requirements under unbalanced voltage conditions for doubly-fed induction generator (DFIG) wind turbines connected to the distribution system. Three different terminal voltage measurement schemes are used and analyzed. The simulations are carried out in EMTP-RV software and the results indicate that for highly imbalanced systems all three phases must be independently analyzed. (AU)

Processo FAPESP: 15/02569-6 - Modelagem, análise e controle de sistemas de energia elétrica operando com geração distribuída
Beneficiário:Rodrigo Andrade Ramos
Modalidade de apoio: Auxílio à Pesquisa - Regular
Processo FAPESP: 13/24570-0 - Estudo de Estabilidade em Sistemas Elétricos de Geração Distribuída com Conexão de Geradores Assíncronos
Beneficiário:Rafael Cruz Borges
Modalidade de apoio: Bolsas no Brasil - Doutorado