| Texto completo | |
| Autor(es): |
Jesus, N. C.
;
Bonatto, B. D.
;
Torquato, R.
;
Cogo, J. R.
;
Duarte, L. M.
;
Sa, G. R.
Número total de Autores: 6
|
| Tipo de documento: | Artigo Científico |
| Fonte: | Electric Power Systems Research; v. 251, p. 13-pg., 2026-02-01. |
| Resumo | |
This paper presents the results and expertise achieved during the monitoring and initial root cause diagnosis of systemic failures in dry-type transformers, which occurred during energization switching of vacuum circuit breakers (pre-strikes). Measurement results obtained during the fault investigation were utilized to effectively confirm the root cause and evaluate the performance of surge protectors. Measurements from 34.5 kV installations without any protection will be presented, as well as real cases involving the application of RC-type surge suppressors and, more recently, a practical application using only surge capacitors. A historical qualitative comparison was conducted, considering results from various measurements in industrial electrical systems. Simulation results, derived from the implementation of a vacuum circuit breaker model in the system using the electromagnetic transients program ATP, will also be presented. (AU) | |
| Processo FAPESP: | 21/11380-5 - CPTEn - Centro Paulista de Estudos da Transição Energética |
| Beneficiário: | Luiz Carlos Pereira da Silva |
| Modalidade de apoio: | Auxílio à Pesquisa - Centros de Ciência para o Desenvolvimento |