Analysis of Fulfillment of LVRT Requirements under Unbalanced Operating Conditions

Full text
Author(s):
Borges, Rafael C. ; Ramos, Rodrigo A. ; Reginatto, Romeu ; IEEE
Total Authors: 4
Document type: Journal article
Source: 2016 IEEE PES TRANSMISSION & DISTRIBUTION CONFERENCE AND EXPOSITION-LATIN AMERICA (PES T&D-LA); v. N/A, p. 6-pg., 2016-01-01.
Abstract

As the wind power penetration continues to increase, wind turbines are required to provide Low Voltage Ride Through (LVRT) capability, thus new grid codes for wind turbines are established. Most grid codes provide the LVRT curve only for the connection to the transmission system. Only few of them include the distribution system and yet the measuring of the terminal voltage do not consider unbalanced operating conditions. This paper analyses the fulfillment of LVRT requirements under unbalanced voltage conditions for doubly-fed induction generator (DFIG) wind turbines connected to the distribution system. Three different terminal voltage measurement schemes are used and analyzed. The simulations are carried out in EMTP-RV software and the results indicate that for highly imbalanced systems all three phases must be independently analyzed. (AU)

FAPESP's process: 15/02569-6 - Modeling, analysis and control of power systems operating with distributed generation
Grantee:Rodrigo Andrade Ramos
Support Opportunities: Regular Research Grants
FAPESP's process: 13/24570-0 - Study of Distributed Generation Systems with the Connection with Asynchronous Generators
Grantee:Rafael Cruz Borges
Support Opportunities: Scholarships in Brazil - Doctorate