A heuristic-based method for setting synchronous distributed generators excitation system parameters to improve islanding detection

Full text
Author(s):
Iscuissati, Rodrigo de Barros ; Davi, Moises Junior Batista Borges ; Vieira, Jose Carlos Melo ; Motter, Daniel
Total Authors: 4
Document type: Journal article
Source: Electric Power Systems Research; v. 235, p. 8-pg., 2024-06-29.
Abstract

Passive anti-islanding protections rely on measurements of voltage, frequency, and rate of change of frequency at the point of common coupling of the distributed generators, and their performance is impacted by the dynamic behavior of distributed generators operating under specific control modes. In this context, this paper proposes a novel heuristic-based method for setting the excitation system parameters of synchronous distributed generators using the differential evolution algorithm to enhance the performance of anti-islanding protection. The results demonstrate that the heuristic-based method achieves improved islanding detection performance compared to traditional values used to specify excitation system parameters. Furthermore, the optimized excitation system parameters do not adversely affect the transient response of the generator during fault events. (AU)

FAPESP's process: 22/00483-0 - Methodology for faults diagnosis in transmission lines with high penetration of inverter-interfaced wind generators
Grantee:Moisés Junior Batista Borges Davi
Support Opportunities: Scholarships in Brazil - Doctorate