Evaluation of processes of removal and inactivation of Giardia spp., Cryptosporidi...
![]() | |
Author(s): |
Marcelo Eustáquio de Carvalho
Total Authors: 1
|
Document type: | Master's Dissertation |
Press: | São Carlos. |
Institution: | Universidade de São Paulo (USP). Escola de Engenharia de São Carlos (EESC/SBD) |
Defense date: | 2003-06-06 |
Examining board members: |
Marco Antonio Penalva Reali;
Maria do Carmo Calijuri;
Bruno Coraucci Filho
|
Advisor: | Marco Antonio Penalva Reali |
Abstract | |
In this wok a sewage sequential treatment consisting of an expanded bed anaerobic reactor (EBAR) with 10 m3/h flow was used, folowed by a high rate DAF containing parallel plates in its interior, with 58 m3/h. For a floculation time of 20 minutes, were studied chemical additives, ferric chlorode dosages of 50 mg/L and 70 mg/L, overflow rates of 21 m/h and 42 m/h, velocity gradients of 60 s-1, 80 s-1 e 100 s-1 and reciculation rate between 8%, 13% and 18%. Among the group of operational conditions of the pilot unit studied high rate DAF the most advantageous was considered: overflow rates of 21 m/h in the high rate DAF of 21 m/h, ferric chlorode dosages of 70 mg/L, velocity gradients of 60 s-1, and air requirements of 8,1 g of air/m3 of wastewater. In those conditions they were obtained the following removals: 84% of turbidez (residual between 6,3 and 62 UT), 73% of DQO (residual\' between 20 and 156 mgO2/L), 75% of phosphorus (residual between 0,5 and 1,9 mgP/L) and 67% of SST (residual between 8 and 80 mg/L of SST). The results demonstrated that the employment of the unit high rate DAF as post-treatment of the anaerobic eflluents provides economy of energy, tends in view they request of 75 to 50% of the amount of air demanded by the systems of conventional flotation. (AU) |