Faulted Phase Selection for Half-Wavelength Power Transmission Lines

Full text
Author(s):
Fabian Espinoza, Renzo G. [1] ; Tavares, Maria Cristina [1]
Total Authors: 2
Affiliation:
[1] Univ Estadual Campinas, Sch Elect & Comp Engn, BR-13083852 Campinas, SP - Brazil
Total Affiliations: 1
Document type: Journal article
Source: IEEE Transactions on Power Delivery; v. 33, n. 2, p. 992-1001, APR 2018.
Web of Science Citations: 2
Abstract

In this paper, a novel faulted phase selection algorithm is proposed to he used for distance protection applied to half-wavelength power transmission lines. These lines represent an alternating current solution for very-long point-to-point interconnections as an alternative to HVDC. However, no such lines are currently in operation, and if this type of line is to be constructed, it will require its own protection philosophy because of its peculiar characteristics. This paper shows that the fault selection algorithms used in conventional relays do not work properly when applied to half-wavelength lines. The algorithm proposed herein is initially studied in the steady state and ultimately implemented in a programmable protective relay that is tested using a real-time simulator. (AU)

FAPESP's process: 15/05626-0 - Contributions to electromagnetic transient and protection studies: application to Brazilian electrical system
Grantee:Maria Cristina Dias Tavares
Support Opportunities: Regular Research Grants