Field Measurements of Non-intentional Emissions above 2 kHz in Photovoltaic Inverter Installations

Full text
Author(s):
Carneiro, Rafael Kotchetkoff ; Yutaka Ota, Joao Inacio ; Pomilio, Jose Antenor ; IEEE
Total Authors: 4
Document type: Journal article
Source: 2020 IEEE 29TH INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS (ISIE); v. N/A, p. 6-pg., 2020-01-01.
Abstract

This paper reports several measurements performed at four installations sites of photovoltaic (PV) systems with a varying number of inverters (ranging from 1 to 5) and with a varying nominal power (ranging from 15 kW to 275 kW). The main aim is to observe non-intentional conducted emissions in the so-called "supraharmonics" frequency range (2 to 150 kHz). Besides confirming the presence of supraharmonics and the resulting voltage distortion, it was observed a 10-s periodic variation of magnitude of a 20-kHz distortion induced by a 4-inverter 53.2-kW PV system. A simplified model is proposed and simulated to analyze and verify this phenomenon, and it is shown that small differences between the switching frequency of PV inverters due to their commutation are the most probable cause of this effect. (AU)

FAPESP's process: 16/08645-9 - Interdisciplinary research activities in electric smart grids
Grantee:João Bosco Ribeiro do Val
Support Opportunities: Research Projects - Thematic Grants
FAPESP's process: 18/13993-1 - STUDY OF SYSTEM STABILITY OF AN ELECTRIC GRID WITH MULTIPLE SOURCES AND CONTROLLED LOADS
Grantee:João Inácio Yutaka Ota
Support Opportunities: Scholarships in Brazil - Post-Doctoral