Advanced search
Start date
Betweenand
(Reference retrieved automatically from Web of Science through information on FAPESP grant and its corresponding number as mentioned in the publication by the authors.)

Application of a robust faulted phase selector to high-resistance and weak-infeed fault conditions on a 1000-kV UHV transmission line

Full text
Author(s):
Espinoza, Renzo Fabian [1, 2] ; Dias, Ozenir [3] ; Tavares, Maria C. [4] ; Molina, Yuri P. [2]
Total Authors: 4
Affiliation:
[1] Itaipu Technol Pk, Foz Do Iguacu, PR - Brazil
[2] Fed Univ Paraaba UFPB, Sch Elect Engn, Joao Pessoa, Paraiba - Brazil
[3] Univ Fed Amazonas, Manaus, Amazonas - Brazil
[4] Univ Campinas UNICAMP, Sch Elect & Comp Engn, Campinas, SP - Brazil
Total Affiliations: 4
Document type: Journal article
Source: Electric Power Systems Research; v. 197, AUG 2021.
Web of Science Citations: 0
Abstract

This work proposes the use of a novel faulted phase-selection phasor-based algorithm to solve the high-resistance and weak-infeed fault condition selection problem in existent long compensated transmission lines. The algorithm was originally developed for future half-wavelength lines (3000 km for 50 Hz system or 2500 km for 60 Hz), and was slightly modified and tested in a real 645 km 1000 kV Ultra High Voltage transmission system. The algorithm was implemented in a programmable protective relay and tested using a real-time simulator. A series of tests under extreme conditions (such as high impedance fault and very week infeed system together) were conducted to evaluate the performance and robustness of the proposed algorithm. (AU)

FAPESP's process: 17/20010-1 - CONTRIBUTIONS TO VERY LONG TRANSMISSION SYSTEM AND POWER SYSTEM PROTECTION