| Full text | |
| Author(s): |
dos Reis, Marcos V. G.
;
Narvaez, Dante, I
;
Moreira, Hugo S.
;
Silva, Joao L. de S.
;
Barros, Tarros A. S.
;
Villalva, Marcelo G.
Total Authors: 6
|
| Document type: | Journal article |
| Source: | IEEE JOURNAL OF PHOTOVOLTAICS; v. N/A, p. 8-pg., 2022-08-22. |
| Abstract | |
High penetration of photovoltaic (PV) inverters in the utility grid is happening in several countries. PV inverters must be able to detect the utility grid disconnection and interrupt the injection of active power. This scenario is known as unintentional islanding. However, islanding detection methods (IDM) are still subject to improvement, especially when considering the high penetration of inverters, making vulnerable IDMs not made for this case. Thus, the purpose of this article is to present a new IDM using dc-link voltage perturbation. The proposed method was defined through an algorithm, and its feasibility was tested through simulations and on an experimental setup with multiple inverters. Several scenarios were analyzed, in which the presented method was able to detect grid disconnections, while other methods failed in multiple inverter scenarios. As a result, the method has proven to be robust, even in the presence of several PV inverters connected at the same point. Furthermore, its implementation is easy and can be included in the inverter control firmware, without requiring any additional hardware. (AU) | |
| FAPESP's process: | 16/08645-9 - Interdisciplinary research activities in electric smart grids |
| Grantee: | João Bosco Ribeiro do Val |
| Support Opportunities: | Research Projects - Thematic Grants |