Advanced search
Start date
Betweenand


Moving average-based mitigation of exponentially decaying DC components

Full text
Author(s):
Menezes, T. S. ; Fernandes, R. A. S. ; Coury, D. V.
Total Authors: 3
Document type: Journal article
Source: Electric Power Systems Research; v. 220, p. 8-pg., 2023-03-11.
Abstract

Exponentially decaying DC components are normally found in current signals during a fault in an electric power system. As these components generally decrease the precision of phasor estimation techniques, they must be filtered out. Thus, this paper proposes an alternative approach to mitigate exponentially decaying DC components. Firstly, the damping factor of the input signal is estimated using its moving average. Then, based on the symmetry of the sinusoidal signal, the value of the exponentially decaying DC component is calculated and subtracted. Tests were conducted with simulated signals, comparing the proposed approach with the state-of-the-art literature. Additionally, all the techniques were embedded in a microcontroller to validate their performances in hardware. Overall, the proposed approach presented the best software performance, compatible with hardware embedded applications in a low-cost microcontroller, proving to be an effective methodology to mitigate the DC offset. (AU)

FAPESP's process: 17/16742-7 - Microgrids:Identification and solution of problems in hybrid distributed generation systems
Grantee:Denis Vinicius Coury
Support Opportunities: Regular Research Grants
FAPESP's process: 21/04872-9 - Evaluating technical impacts on the expansion of distributed generation for smart grids
Grantee:Denis Vinicius Coury
Support Opportunities: Regular Research Grants